If the
frequency of operation of pumping liquid into a tank is to frequent, too much
stress is subjected to a single motor pump. In such case the life span of the
motor may not last long. To avoid to much stress to a single motor pump, it is
wise to add another motor pump. The two motor are design to operate
alternately. Figure (A) illustrate two motor pumps that alternately pumps liquid
into tank.
Control Operation
Figure (B) illustrate the schematic diagram of the control circuit of the “Alternate
Operation of a Two Motor Pump”. Closing the toggle switch SW will place the
control circuit ready for operation.
As the
liquid level in the tank drops to the lower limit LL as shown in figure (A).
The float switch* contact FS (1-2) will close, see figure (B). Contactor M1
(A-B) is energize by the current that flows from the line L1, toggle switch SW,
float switch FS (1-2), contact M2 (11-12), contact R (11-12), contactor M1
(A-B) and to line L2. contact M1 (13-14) will close to maintain contactor M1
(A-B) continuously energized. Contact M1 (11-12) will open to prevent contactor
M2 (A-B) from being energized. Contact M1 (1-2) will close to energize relay R
(A-B).
*For the
detail operation of the float switch FS (1-2), refer to Article 10.0 entitle
“Float Switch Motor Pump Control”.
With relay
R (A-B) energize, contact R (1-2) will close to maintain relay R (A-B) continuously energized. Contact R (13-14)
will close and contact R (11-12) will open. At this condition, the motor pump
M11, controlled by contactor M1 (A-B), will pump liquid into the tank. The
float switch FS (1-2) remains close as the liquid in the tank rises up.
Advertisement
When the
liquid reaches the upper limit UL, the float switch contact FS (1-2) will open.
This de-energize contactor M1 (A-B) to stop the motor pump M11 from pumping
liquid into the tank. Also contacts M1 (13-14) and M1 (1-2) will open. Contact
M1 (11-12) will open. As liquid is drain from the tank and its level drops, the
float switch FS (1-2) remains open. Relay R (A-B) is still energized.
(A)
Liquid tank with two
motor pump.
When the
level of the liquid reaches the lower limit LL, the float switch FS (1-2) will
close again. Contactor M2 (A-B) is energized by the current that flows from
line L1, toggle switch SW, float switch FS (1-2), contact M1 (11-12), contact R
(13-14) which is now closed, contactor M2 (A-B) and to line L2. contact M2
(11-12) will open to prevent contactor M1 (A-B) from being energized. Contact
M2 (13-14) will close to maintain contactor M2 (A-B) continuously energized.
Contact M2 (21-22) will open to de-energized relay R (A-B).
With relay R (A-B)
ed-energized, contact R (11-12) will close, and contacts R (13-14) and (1-2)
will open. At this condition the motor pump M22 controlled by contactor M2
(A-B) will pump liquid into the tank. The float switch FS (1-2) remains close
as the liquid in the tank rises up.
(B)
Control circuit
diagram of the “Alternative Operation of
Two Motor Pumps”
When the
liquid level reach again the upper limit UL, the float switch contact FS (1-2)
opens. This de-energize contactor M2 (A-B) and stops the motor pump M22 from
pumping liquid into the tank. Contacts M2 (11-12) and M2 (21-22) will close and
contact M2 (13-14) will open. The condition of the circuit is brought back to
the shown in figure (B). Alternate operation of the motor pump M11 and M22
is repeated as the liquid alternately rises up and drop down.
Note: If
the float switch FS in the laboratory are insufficient,
they can be substituted with an ordinary ON-OFF toggle switches or micro switches.
Read Next Article:---> PRESSURE OPERATED CONTROL SYSTEM (POCS)
Back to Previous Article:<--- TIME SIGNAL SYSTEM
Read Next Article:---> PRESSURE OPERATED CONTROL SYSTEM (POCS)
Back to Previous Article:<--- TIME SIGNAL SYSTEM
great perfect...
ReplyDeletehow about 3 alternating motors
ReplyDeletehow about 3 alternating motors
ReplyDeleteLongtime ago, I have read the circuit in Electrician book. I forgot to copy it. Today, I try to find again for many days, but I can't. This is the circuit which your posting on that I find. I have found. Thanks so much.
ReplyDeleteThis article helped us today. It made our job and our day easier. Thanks.
ReplyDeleteThis comment has been removed by the author.
ReplyDeleteWhen I hooked it up right and put the relay line before the floats it worked like a champ, hope I didn't discourage anyone, great setup!
DeletePlz make with three alternating motor
ReplyDeleteExaclty, also required Pump Control Panel for damage protection
ReplyDeleteThanks for sharing it I like more control diagram.
ReplyDeleteVery much thankful for your this type content
What kind of relay did they used for this control thank you so much for the rply
ReplyDeleteDc gear motor 37mm diameter
ReplyDeleteWidly useful 37mm diameter 12v 24v 6v JGB37-520 electric high rpm high torque dc gear motor for Electric Bicycle
Model: JGB37-520
To Buy Click Here: Dc gear motor 37mm diameter
Awesome
ReplyDeletenice and well diagram
ReplyDeleteGreat
ReplyDelete
ReplyDeleteSubmersible pumps in Chandigarh are best provided by Aquasol for all your needs. Compact, efficient and durable, the Aquasol pumps are recommended for irrigation, water and sewage supply as well as drainage purposes. Show everyone that the only place to go for state-of-the art technology and reliable water pumping is with Aquasol!